Voltage Performance Analysis with Integration of Utility Scale Solar PV Plant in Bangladesh National Grid
No Thumbnail Available
Date
2020-11-02
Journal Title
Journal ISSN
Volume Title
Publisher
IEEE 2020 IEEE Region 10 Symposium (TENSYMP), Dhaka, Bangladesh, 2020
Abstract
The aim of this paper is to analyze the voltage performance due to integration of an utility scale Solar Photovoltaic Generation (SPVG) in Bangladesh national grid. Voltage profile in a power system is a major concern for supplying quality power to consumers. Integration of SPVG in a relatively weaker part of a grid may require reactive power
compensation to retain acceptable voltage level. In this paper, detailed investigations are carried out to explore
the impact of 8 MW SPVG at a 33 kV bus of northern zone of Bangladesh power system. In addition, static voltage stability analysis is executed using continuation power flow method. Afterwards, reactive power compensation is done using capacitor bank to maintain the required voltage to integrate SPVG to the grid. All the simulations are performed based on practical operating scenarios of Bangladesh power system using DIgSILENT PowerFactory software.
Description
NA
Keywords
SPVG, P-V curve, Loadability margin, Voltage stability, Reactive compensation